ELEC209 ELECTRICAL CIRCUITS & POWER SYSTEMS

联系我们: 手动添加方式: 微信>添加朋友>企业微信联系人>13262280223 或者 QQ: 1483266981

Answer ALL Questions.
Further Information:
You must provide your solutions with all necessary details and relevant steps. Failure to do this
results in losing marks. Marks are allocated for steps as well as final answers, so you must show all
relevant intermediate steps.
PAPER CODE NO. EXAMINER: Dr. A. Al-Ataby
ELEC209 DEPARTMENT: EE&E Email: aliataby@liverpool.ac.uk

1. a) The switch in the circuit shown in Figure Q1-1 has been closed for a long time and is
opened at = 0.
Figure Q1 – 1
i) Calculate the initial value of the current . 3
ii) Calculate the initial energy stored in the inductor. 2
iii) What is the time constant of the circuit for > 0 2
iv) What is the mathematical expression for ( ) for ≥ 0 4
v) What percentage of the initial energy stored in the inductor has been dissipated
in the 2 resistor at 5 ms after the switch has been opened.
4
b) There is no energy stored in the circuit shown in Figure Q1-2 at the time the switch is
closed. Find the mathematical expressions for ( ), ( ), 1
( ) and 2( ) for ≥ 0.
2 H i i1 4 H i2
18 H +
_
vo 100 V +
–
(50/3)
t = 0
Figure Q1-2
10
Total
25
120 V 6
8 mH
i +
–
3
30 2 t = 0

2. a) A balanced three-phase Y-connected generator has an internal impedance of 0.2 +
0.5 per phase and an internal voltage of 120 V per phase. The generator feeds a
balanced three-phase -load having an impedance of 118.5 + 85.8 per phase.
The impedance of the line connecting the generator to the load is 0.3 + 0.9 per
phase. Assume the system has a positive phase sequence.
i) Calculate the three line currents. 3
ii) Calculate the three phase voltages at the load. 3
iii) Calculate the three phase currents of the load. 3
iv) Calculate the efficiency of the given three-phase system. 2
b) A balanced three-phase load requires 600 kW at a lagging power factor of 0.7. The
load is fed from a line having an impedance of 0.003 + 0.02 per phase. The line
voltage at the terminal of the load is 500 V.
i) Calculate the magnitude of the line current 2
ii) Calculate the magnitude of the line voltage at the sending end of the line. 4
iii) Calculate the power factor at the sending end of the line. 2
iv) Calculate the transmitted (i.e. the sending end) power. 2
c) Two sets of measurements are made on a two-port resistive circuit. The results are
as follows:
Port 2 Open Circuited
Port 2 Short Circuited
1 = 10 mV 1 = 24 mV
1 = 10 μA 1 = 20 μA
2 = -40 V 2 = 1 mA
Use a suitable two-port network parameters to represent the circuit.
4
Total
25

3. a) A power transmission line is represented by a series impedance = 5 + 40
. Assuming the base voltage is 140 kV (line) and the base power is 20 MVA
(three-phase power),
i) Express transmission line impedance in per unit. 3
ii) Find the base current of the system. 3
b) A power system is shown in Figure Q3 below. Draw a simpler representation
(i.e. equivalent circuit) for this system using the per unit concept. Show all the
necessary steps (Note: Use 30 kVA and 240 V as your base values for the
entire system. Reactances X1 and X2 are expressed in per unit, pu).
Figure Q3
10
Question continues overleaf.
Line T1 T2
30 kVA X1 = 0.1 pu 20 kVA X2 = 0.2 pu
ZL = 0.8 + j0.3 240 V 480 V 460 V 115 V j5 Load VS = 230∠0o V

Question continued.
c) It is required to replace a fossil fuel power plant by a wind farm, and you have
been hired as the engineer to carry out this task. After studying the site, you
have found out that the average wind speed is 13 m/s. You have decided to use
wind turbines with 42% efficiency and 50 m blade length. Design the farm
(i.e. determine the number of wind turbines needed to replace the power
plant), assuming the density of air is 1.25 kg/m3
and the fossil fuel power plant
generates 750 MW on average. [Note: the number of turbines must be an
integer].
6
d) A three-phase synchronous generator with terminal line voltage of 60 kV is
required to have line current of 6.5 -40 kA. Determine the complex power
supplied by the generator and the power factor.
3
Total
25

4. a) A three-phase 4-pole induction machine, with rated frequency of 50 Hz and rated
voltage of 380 V, has the following parameters: 1 = 0.5 , 2
′ = 0.2 , 1 = 0.4
and 2
′ = 0.4 . (Assume the rated speed is 1455 rpm).
i) Calculate the rated slip. 3
ii) Calculate the starting and rated stator currents. 4
iii) Calculate the input power and the power factor of the machine under rated
condition.
2
b) A three-phase, 10 kV, 750 MVA, star-connected synchronous generator has a per
phase reactance of 2 pu and supplies 1.2 pu per phase real power at the rated
voltage, with a leading power factor of 0.75 to the load.
i) Calculate the actual excitation voltage and the power angle. 4
ii) Calculate the actual complex power consumed by the load. 4
iii) Is the generator overexcited or under excited Explain your answer. 2
c) When filling the fuel tank of a truck with an internal combustion engine, it takes 3
minutes to put 100 litres into the tank. Given that the density of petrol is 730 kg m-3
and its heat value 45 MJ kg-1
, calculate the effective energy flow rate while filling
the tank.
4
d) The turns ratio of a transformer is 20:3. Calculate the referred load to the primary
side of this transformer when the load connected to the secondary winding is 10 +
5 .
2

发表评论

了解 KJESSAY历史案例 的更多信息

立即订阅以继续阅读并访问完整档案。

继续阅读